Tripp Lite
Tripp Lite SU5000RT 5000VA 4500W 3U Rack/Tower UPS
Provides 5000VA 4500W online double-conversion backup with hardwire or L6-30P input and multiple 200–250V output options in a 3U rack/tower form
- Online double-conversion topology protects critical loads from all power disturbances
- 5000VA/4500W rating supports high-density server and network equipment
- Wide 200–250V input window with AVR corrects voltage without battery use
- Hardwire or L6-30P input with 10 ft cord fits existing 30A electrical service
- 3U rack/tower form factor deploys in standard cabinets or floor-standing installations
5000 VA double-conversion UPS
The Tripp Lite SU5000RT is a 5000 VA, 4500 W double-conversion UPS built for 3U rack or tower installation. It accepts single-phase input from 200 V to 250 V AC with a factory default of 208 V and a rated maximum input current of 23.3 A. The unit ships with a 10 ft hardwire or L6-30P input cord and requires a 30 A upstream breaker. It provides output through two L6-20R and two L6-30R receptacles.
Online topology for continuous conditioning
Because the inverter runs continuously, the output voltage stays regulated without transferring to battery during sags, surges or frequency drift. This topology isolates connected equipment from raw mains disturbances at all times, making it suitable for servers, network gear and sensitive electronics that cannot tolerate a switchover delay. The internal batteries deliver approximately three minutes of run-time at full load, enough for orderly shutdown scripts to complete.
Efficient operation with managed heat
Double-conversion efficiency reduces waste heat compared with legacy designs, so the unit runs cooler inside a crowded rack. Fan speed scales with load and temperature, keeping acoustic output low during typical partial-load operation. The 30 A service recommendation matches the hardwire or L6-30P input, ensuring the supply wiring and breaker stay within thermal limits without oversizing.
Highlights
- Online double-conversion topology protects critical loads from all power disturbances
- 5000VA/4500W rating supports high-density server and network equipment
- Wide 200–250V input window with AVR corrects voltage without battery use
- Hardwire or L6-30P input with 10 ft cord fits existing 30A electrical service
- 3U rack/tower form factor deploys in standard cabinets or floor-standing installations
Specifications
| Brand | TRIPP LITE |
|---|---|
| Shipping weight | 48.08 kg |
| Package size | 686 × 439 × 130 mm |
Questions about this item
How loud and hot does the SU5000RT get when it runs at full load all day?
The unit draws up to 23.3 A at 208 V input and is rated for 4500 W output; fan speed and heat rise will scale with that load, so expect noticeable airflow and warmth in a closed rack.
What electrical service and wiring must already be in place before the SU5000RT can be installed?
A 30 A single-phase circuit with either a hard-wire feed or an L6-30P receptacle is required, and the supplied input cord is 10 ft long.
Will the SU5000RT protect older 200 V or 240 V equipment connected to its L6-20R and L6-30R outlets?
Yes — the UPS accepts 200 V, 208 V, 220 V, 230 V, 240 V and 250 V nominal inputs and delivers 230 V or 240 V output, so legacy gear within that range is supported.
New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.
Also in this aisle
People compared these
Same shelf, same checkout — eight coins and a 30-minute rate lock.
YOUHUA SATA Cable Kit 2×Data 0.48 m 2×Power 0.16 m
- Sata cables: 2 SATA…
Micro Connectors SATA cable 40 inches straight to right angle locking latch black 3 pack
- Black