We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

CyberPower

CyberPower OL1KRM UPS 1000VA 800W 8x NEMA 5-15R

SKU CH-4NA6-51F3S MPN OL1KRM

Rack-mountable double-conversion UPS delivers 1000 VA and 800 W through eight NEMA 5-15R outlets with 4-minute full-load runtime

  • International Version120V
  • Input Voltage Range100 - 125V
  • Input Frequency40 - 70 Hz
  • Input ConnectionNEMA 5-15P
  • VA Rating1000 VA
  • Watts800 Watts
  • Online double-conversion topology delivers clean sine-wave power
  • Configurable 100/110/115/120/125 V output matches sensitive equipment
  • Eight NEMA 5-15R outlets support multiple rack devices
  • 4 min full-load / 11.5 min half-load runtime protects critical loads
  • USB and serial ports enable automated monitoring and shutdown

Double-Conversion Online UPS

The CyberPower OL1KRM is a rack-mountable uninterruptible power supply that uses double-conversion online topology to deliver clean sine-wave output. It accepts 100 to 125 VAC input at 40 to 70 Hz and provides configurable output at 100, 110, 115, 120 or 125 VAC within two percent regulation. Eight NEMA 5-15R outlets supply up to 800 watts or 1000 VA from a single NEMA 5-15P input.

Suited For And Not Suited For

This unit suits network closets, server racks and workstations that require continuous voltage regulation and zero transfer time during power events. USB and serial ports enable management integration. Buyers needing longer battery runtime at full load or higher wattage capacity should consider larger models. Environments outside the zero to forty degree Celsius operating range or requiring non-standard outlet types are not a fit.

Capacity And Headroom

At full 800-watt load the internal sealed lead-acid batteries provide four minutes of runtime, extending to 11.5 minutes at half load. Recharge from empty to ninety percent takes four hours. Overload protection allows brief excursions to 130 percent for twelve seconds in line mode before bypass, and to 150 percent for two seconds before shutdown. Surge energy rating is 710 joules.

Highlights

  • Online double-conversion topology delivers clean sine-wave power
  • Configurable 100/110/115/120/125 V output matches sensitive equipment
  • Eight NEMA 5-15R outlets support multiple rack devices
  • 4 min full-load / 11.5 min half-load runtime protects critical loads
  • USB and serial ports enable automated monitoring and shutdown

Specifications

BrandCyberPower
SeriesEssential Online UPS
ModelOL1KRM
International Version120V
Input Voltage Range100 - 125V
Input Frequency40 - 70 Hz
Input ConnectionNEMA 5-15P
VA Rating1000 VA
Watts800 Watts
Output Voltage100/110/115/120/125 VAC +/- 2% (configurable)
Outlets8
Outlet Type8 x NEMA 5-15R
Battery TypeSealed Lead Acid
Battery Run Time4 min Full Load / 11.5 min Half Load
Battery Recharge Time4 Hours (0% to 90% charged)
Battery ReplaceableRB1270X2G
AlarmsBattery Mode
Low Battery
Overload
UPS Fault
Interface PortUSB, Serial
ApprovalsUL 1778
CSA C22.2 NO.107.3
FCC Part 15 Class B
RackmountableYes
Surge Energy Rating710 Joules
ProtectionUPS Output Cut Off Immediately or Input Fuse
Circuit Breaker Protection
Overload Protection:
Line Mode: 102% to 130% load for 12s - bypass
Line Mode: 131% to 150% load for 2 s - bypass
>150% load 300ms -no output
Battery Mode: 102% to 130% load for 12 s - shutdown
Battery Mode: >130% for 2 s -shutdown
Bypass Mode: 102% to 110% warning
Bypass Mode: 111% to 130% load for 5min - no output
Bypass Mode: 131% to 150% 16s - no output
>150% for 300ms - no output
TemperatureOperating Temperature: 32 - 104 °F (0 - 40 °C)
Storage Temperature: 5 - 113 °F (-15 - 45 °C)
HumidityOperating Relative Humidity: 0 - 0.9 % (non-condensing)
Storage Relative Humidity: 0 - 0.95% (non-condensing)
Dimensions3.41" x 17.05" x 11.22"
Weight26.46 lbs.
Shipping weight15.80 kg
Package size560 × 390 × 240 mm

Questions about this item

What input plug does the OL1KRM need from my wall circuit?

The unit ships with a NEMA 5-15P input cord, so a standard 120 V 15 A receptacle is required.

Will my older 100 V equipment run safely on the configurable output?

Yes, the output can be set to 100 V ±2%, matching legacy 100 V gear while the UPS accepts 100–125 V input.

How do I confirm the double-conversion topology is active after installation?

Connect the USB or serial port and use the management software to verify the UPS reports Online mode with output voltage regulated to the selected 100/110/115/120/125 V setting.

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.

Also in this aisle