Tripp Lite
Tripp Lite PDUMNH30HV 2U Monitored PDU 208/240V 30A 12 C13 4 C19 L6-30P 12ft
A 2U rackmount PDU distributes 208/240V power through twelve C13 and four C19 outlets with a 30A L6-30P input and built-in load monitoring
- TypeMonitored
- Rack Size2U
- StyleRackmount
- Front Panel LEDsTwo LEDs with toggle button identify which bank the visual c
- CertificationsTested to UL (USA), CSA (Canada), NOM (Mexico), Class A (emi
- ROHSYes
- Monitored load, voltage and frequency over built-in network interface
- 16 outlets: 12 C13 and 4 C19 for dense rack deployments
- Two 20 A circuit breakers protect separate outlet banks
- 2U steel chassis fits standard 19-inch racks
- 12 ft L6-30P cord reaches distant power sources
2U Monitored PDU for 30A Single-Phase Racks
This monitored power distribution unit fits a 2U rack space and delivers 208/240V output from a single-phase 30A input. Twelve C13 and four C19 outlets provide sixteen total connections for servers and network gear. A built-in network interface reports load level, input voltage and frequency for remote monitoring.
Verify L6-30P Supply and Breaker Capacity
Confirm the facility provides a 208/240V single-phase feed terminated with an L6-30P receptacle rated for 30A. The twelve-foot cord reaches the rack inlet without extension cords. Each of the two outlet banks is protected by a 20A circuit breaker, so combined draw on any bank must stay within that limit.
Sustained Load Monitoring and Thermal Limits
The front-panel LEDs toggle between bank 1, bank 2 or combined current readings for real-time visibility during continuous operation. Steel construction and convection cooling support 0-95% non-condensing humidity environments. Network reporting allows trend tracking to prevent gradual overload rather than relying on instantaneous trip behaviour.
Highlights
- Monitored load, voltage and frequency over built-in network interface
- 16 outlets: 12 C13 and 4 C19 for dense rack deployments
- Two 20 A circuit breakers protect separate outlet banks
- 2U steel chassis fits standard 19-inch racks
- 12 ft L6-30P cord reaches distant power sources
Specifications
| Brand | Tripp Lite |
|---|---|
| Model | PDUMNH30HV |
| Type | Monitored |
| Rack Size | 2U |
| Style | Rackmount |
| Front Panel LEDs | Two LEDs with toggle button identify which bank the visual current meter is reporting (bank 1, bank 2 or banks 1 & 2 combined) |
| Certifications | Tested to UL (USA), CSA (Canada), NOM (Mexico), Class A (emissions), RoHS compliant |
| ROHS | Yes |
| Input Voltage | 208/240V |
| Maximum Input Current | 30A |
| Input Connector(s) | L6-30P 30A 208/240V input plug |
| Cord Length | 12 ft |
| Output Voltage | 208/240V |
| Output Frequency | 50/60Hz |
| Output Connector(s) | 12 C13, 4 C19 outlets |
| Overload Protection | Outlets are arranged in two banks of 8 (6 C13, 2 C19 per bank); Each bank is protected by a separate 20A circuit breaker |
| Storage Relative Humidity | 0-95% non-condensing |
| Features | Input connection type: L6-30P Plug Type: L6-30P PDU Plug Type: NEMA L6-30P Phase: Single-Phase Material of construction: Steel Reports PDU load level, input voltage and frequency over built-in network interface with options for environmental and security monitoring Digital current meter offers visual current monitoring Cord retention brackets keep vital equipment plugs connected |
| Dimensions | 3.5" x 17.5" x 12.5" |
| Weight | 13.7 lbs. |
| Shipping weight | 7.98 kg |
| Package size | 521 × 432 × 203 mm |
Questions about this item
What outlets and input plug does the PDU ship with, and are mounting brackets or a network cable included?
The unit provides twelve C13 and four C19 outlets on the front and a NEMA L6-30P plug on a 12 ft cord. Rack-mount brackets are built into the 2U steel chassis; a network patch cable for the monitoring port is not supplied.
How do the two 20 A breaker banks affect which capacity to select for a 30 A feed?
Each of the two banks carries six C13 and two C19 outlets and is protected by its own 20 A breaker, so total usable load is limited to 40 A across both banks but no single bank may exceed 20 A.
What does the front-panel current meter actually show when the PDU is powered?
A toggle button cycles the LED meter between bank 1, bank 2, or the combined 30 A input current, while the network interface reports real-time load, voltage and frequency for remote monitoring.
New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.
Also in this aisle
People compared these
Same shelf, same checkout — eight coins and a 30-minute rate lock.