SQUARE D
SQUARE D 9013FS Pressure Switch 20-40PSI DPST
Controls water pumps at 20-40 PSI with DPST contacts rated for 10 A at 120/240 V
- TypeLight Switch
- Factory-set 20/40 psi range suits common water-pump cycles
- DPST contacts handle 10 A for reliable motor switching
- Rated 1½ hp at 120 V and 2 hp at 240 V single-phase
- Operates from -22 °F to 257 °F for harsh environments
- NEMA 1 enclosure protects switch mechanism indoors
Water-pump pressure switch
The Square D 9013FS is a DPST pressure switch designed to control water-pump motors automatically. It operates on a factory-set 20 to 40 psi range with a 15 to 30 psi adjustable differential. The single 1/4 in FNPT port connects directly to the pump system. NEMA 1 rating limits use to indoor or protected locations.
Motor-load capacity and pressure limits
The switch handles 1 1/2 hp at 120 V single-phase, 2 hp at 240 V single-phase, 3 hp at 240 V three-phase and 1 hp at 480 V three-phase. Pressure settings can be adjusted anywhere from 5 to 65 psi, but the differential cannot be set below 15 psi or above 30 psi. Operating temperature spans -22 to 257 degrees F, so extreme cold or heat beyond that range is not supported.
Manual auto-off lever and wiring format
A manual Auto/Off lever on the cover lets the user disable automatic cycling without rewiring. The DPST contact form breaks both lines simultaneously for positive motor disconnect. No unloader valve is included, so systems requiring head-pressure relief need a separate unloader. The 10 A contact rating suits the listed motor loads without additional relay.
Highlights
- Factory-set 20/40 psi range suits common water-pump cycles
- DPST contacts handle 10 A for reliable motor switching
- Rated 1½ hp at 120 V and 2 hp at 240 V single-phase
- Operates from -22 °F to 257 °F for harsh environments
- NEMA 1 enclosure protects switch mechanism indoors
Specifications
| Brand | Square D |
|---|---|
| Type | Light Switch |
Questions about this item
Will the 9013FS pressure switch control my existing 120 V 1 1/2 hp water pump motor?
Yes, the switch is rated for 1 1/2 hp at 120 V single phase, matching that motor.
How can I verify the 9013FS is cycling at the correct 20-40 psi range after installation?
Watch the system pressure gauge; the pump should start at 20 psi and stop at 40 psi.
Does the 9013FS come with a pressure gauge or unloader valve, or must I buy them separately?
The switch includes no gauge and no unloader valve; both must be purchased separately.