We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

CyberPower

CyberPower PR3000RTXL2UHVACN 3000VA/3000W UPS

SKU CH-RMZ2-96VK2 MPN PR3000RTXL2UHVACN

Rack or tower line-interactive UPS delivers 3000 VA and 3000 W pure sine-wave output at 200–240 VAC with six NEMA outlets, 2430 J surge protection and 10.7 min half-load runtime

  • Input Voltage Range131 - 302V
  • Input Frequency47 - 63 Hz
  • Input ConnectionNEMA L6-20P
  • VA Rating3000 VA
  • Watts3000 Watts
  • Output Voltage200/208/220/230/240 VAC +/- 5%
  • Pure sine wave output protects sensitive equipment
  • Line-interactive topology with AVR conserves battery life
  • 3000 VA / 3000 W capacity runs critical loads
  • 6 outlets: four NEMA 6-20R and two NEMA L6-20R
  • LCD panel rotates 90 degrees for 47 real-time settings

Smart App Sinewave UPS for servers

The CyberPower PR3000RTXL2UHVACN is a 3000VA/3000W line-interactive UPS that delivers pure sine wave output at 200-240VAC. It protects sensitive servers, network gear and storage arrays from outages and power anomalies. Six battery-backed outlets keep critical loads running during utility failures. The 2U rack/tower chassis fits standard enclosures or stands upright on a shelf.

Verify input plug and outlet needs

Your facility must supply a NEMA L6-20P receptacle on a 200-240V circuit. Confirm the UPS input voltage range of 131-302VAC covers local mains conditions. Check that connected equipment uses NEMA 6-20R or L6-20R plugs; four 6-20R and two L6-20R outlets are provided. Ensure total attached load does not exceed 3000W. Serial and dry-contact ports are available for management integration.

Toolless battery access and rotating LCD

The front panel removes without tools and captive screws secure the battery door for quick RB1260X8 replacement. A colour-coded rear panel simplifies cable routing during installation. The LCD rotates 90 degrees and tilts for readable status in rack or tower orientation, displaying 47 configurable settings. Surge protection is rated at 2430 joules. Battery recharge reaches 90% capacity in three hours.

Highlights

  • Pure sine wave output protects sensitive equipment
  • Line-interactive topology with AVR conserves battery life
  • 3000 VA / 3000 W capacity runs critical loads
  • 6 outlets: four NEMA 6-20R and two NEMA L6-20R
  • LCD panel rotates 90 degrees for 47 real-time settings

Specifications

BrandCyberPower
SeriesSmart App Sinewave
ModelPR3000RTXL2UHVACN
Input Voltage Range131 - 302V
Input Frequency47 - 63 Hz
Input ConnectionNEMA L6-20P
VA Rating3000 VA
Watts3000 Watts
Output Voltage200/208/220/230/240 VAC +/- 5%
Output Frequency50/60 Hz +/- 1%
Outlets6
Outlet Type4 x NEMA 6-20R
2 x NEMA L6-20R
Battery TypeSealed Lead Acid
Battery Run TimeRuntime at Full Load: 3.6 min
Runtime at Half Load: 10.7 min
Battery Recharge Time3 Hours (0% to 90% charged)
Battery ReplaceableRB1260X8
AlarmsBattery Mode
Low Battery
Overload
Overcharge
Fault
Interface Port1 Serial, 1 Dry Contact
RackmountableYes
Surge Energy Rating2430 Joules
ProtectionInternal Circuitry Limiting
Circuit Breaker Protected
Dimensions17.1" x 3.4" x 24.8"
Weight87.5 lbs.
Shipping weight48.53 kg
Package size765 × 574 × 274 mm

Questions about this item

What comes in the box and which cables or accessories must be purchased separately?

The unit ships with a 10 ft NEMA L6-20P input cord, four NEMA 6-20R outlets, two NEMA L6-20R outlets, a serial port, a dry-contact port and an LCD panel; no extra cables are included.

The spec sheet lists 3000 VA and 3000 W — which capacity should I choose for my load?

Both ratings are identical at 3000, so size the UPS to the total wattage of your connected equipment; do not exceed 3000 W.

What does the 3.6-minute full-load runtime mean once the UPS is installed in my rack?

At the full 3000 W load the battery will support connected gear for 3.6 minutes; at half load the runtime extends to 10.7 minutes.

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.

Also in this aisle

People compared these

Same shelf, same checkout — eight coins and a 30-minute rate lock.