We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

CyberPower

CyberPower OL5KRTHDL 5000VA 5000W UPS

SKU CH-CWRZ-K4K0G MPN OL5KRTHDL

Double-conversion online UPS delivers 5000 VA and 5000 W pure sine-wave power with 4.9 minutes runtime at full load and 14.3 minutes at half load

  • International Version120V
  • Input Voltage Range120-139 VAC for 0-25% Load 140-159 VAC for 0-50% Load 160-17
  • Input Frequency40 - 70 Hz
  • Input ConnectionNEMA L6-30P
  • VA Rating5000 VA
  • Watts5000 Watts
  • Double-conversion topology delivers clean sine-wave power
  • Unity power factor provides full 5000 W usable capacity
  • 3U rack/tower form factor fits dense deployments
  • 2430 joule surge rating shields connected equipment
  • Hot-swappable battery module enables zero-downtime replacement

High-density 5000 VA online UPS

The CyberPower OL5KRTHDL is a double-conversion UPS rated at 5000 VA and 5000 W with unity power factor. It accepts 120 V to 280 VAC input and provides user-configurable output at 200, 208, 220, 230 or 240 VAC. The unit fits in a 3U rack or tower form factor and includes a pre-installed network management card for remote monitoring of up to 50 clients. Buyers needing longer runtime at full load or additional outlet count should consider other models.

ECO mode efficiency and sine-wave output

GreenPower UPS ECO Mode delivers up to 96 percent efficiency to reduce power consumption and thermal dissipation. The sine-wave output ensures clean power for sensitive equipment across the full 0 to 100 percent load range. Audible alarms signal battery mode, low battery, overload and UPS fault conditions. A serial interface port provides basic local connectivity alongside the network card. The unit is not suited for environments requiring silent fanless operation.

Hardwire terminal with locking outlets

A NEMA L6-30P power cord is included and a hardwire terminal option is available for permanent installation. Four locking outlets comprise two NEMA L6-20R and two NEMA L6-30R receptacles. Sealed lead-acid batteries recharge from zero to 90 percent in four hours and use replaceable RB1290X12 modules. Surge energy rating is 2430 joules with input fuse and circuit breaker protection. Installers without access to 30 A locking circuits or hardwire feeds cannot use this unit directly.

Highlights

  • Double-conversion topology delivers clean sine-wave power
  • Unity power factor provides full 5000 W usable capacity
  • 3U rack/tower form factor fits dense deployments
  • 2430 joule surge rating shields connected equipment
  • Hot-swappable battery module enables zero-downtime replacement

Specifications

BrandCyberPower
SeriesSmart App Online UPS
ModelOL5KRTHDL
International Version120V
Input Voltage Range120-139 VAC for 0-25% Load
140-159 VAC for 0-50% Load
160-179 VAC for 0-75% Load
180-280 VAC for 0-100% Load
Input Frequency40 - 70 Hz
Input ConnectionNEMA L6-30P
VA Rating5000 VA
Watts5000 Watts
Outlets4
Outlet Type2 x NEMA L6-20R
2 x NEMA L6-30R
Battery TypeSealed Lead Acid
Battery Run TimeRuntime at Full Load: 4.9 min
Runtime at Half Load: 14.3 min
Battery Recharge Time4 Hours (0% to 90% charged)
Battery Replaceable(1) RB1290X12
AlarmsBattery Mode
Low Battery
Overload
UPS Fault
Interface PortSerial
RackmountableYes
Surge Energy Rating2430 Joules
ProtectionUPS Output Cut off Immediately
Input Fuse / Circuit Breaker Protection
Dimensions17" x 5.1" x 28.3"
Weight118 lbs.
Shipping weight90.72 kg
Package size889 × 599 × 452 mm

Questions about this item

How do I wire the hardwire terminals on the OL5KRTHDL, and which step is often missed?

Connect the input L6-30P cord or hardwire the 200-240 VAC supply to the terminals, then attach loads to the two L6-20R and two L6-30R outlets; the step often missed is configuring the output voltage to 200, 208, 220, 230 or 240 VAC via the LCD before powering on.

Which battery pack replaces the internal cells, and when should I plan the swap?

The replaceable pack is the RB1290X12; expect roughly four hours to recharge from 0 to 90 percent, so schedule replacement when runtime at full load drops below the rated 4.9 minutes or at half load below 14.3 minutes.

What thermal or overload limit triggers first during sustained full-load operation?

At 5000 W the UPS will sound the overload alarm and cut output immediately if the load exceeds 100 percent; the 2430 joule surge rating and input fuse/breaker protect the input side, but the output cutoff is the first active limit under continuous full load.

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.