We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

CyberPower

CyberPower OL10KRTHD 10000VA 10000W UPS

SKU CH-CJRT-MDZYM MPN OL10KRTHD

Provides 10000 VA double-conversion backup with sine-wave output, hardwire input, seven outlets and 4U rack/tower form factor

  • International Version120V
  • Input Voltage Range120-139 VAC for 0-25% Load 140-159 VAC for 0-50% Load 160-17
  • Input Frequency40 - 70 Hz
  • VA Rating10000 VA
  • Watts10000 Watts
  • Outlets7
  • Double-conversion topology delivers clean sine-wave output
  • Unity power factor provides 10000 W from 10000 VA rating
  • User-configurable 200/208/220/230/240 VAC output ±2 %
  • Seven outlets: four L6-20R, two L6-30R, one hardwire terminal
  • Four-hour recharge to 90 % with replaceable RB1290X8 batteries

Capacity and Topology

The CyberPower OL10KRTHD is a new double-conversion online UPS rated at 10000 VA and 10000 W with a unity power factor. It accepts a 120 V international input range from 120 to 280 VAC depending on load percentage and provides user-configurable sine-wave output at 200, 208, 220, 230 or 240 VAC. The unit fits in a 4U rack or tower form factor and includes a hardwire terminal block plus six locking outlets.

Suitable Installations and Limitations

This UPS suits data centres, server rooms or industrial sites that require hardwired three-phase compatible power with extended runtime options via external battery packs. It is not intended for desktop or workstation users who need standard NEMA 5-15R outlets or plug-and-play USB monitoring. Buyers without professional electrical installation capability should consider alternative models with corded input connections.

Decisive Specification

The 2.4 minute runtime at full 10000 W load determines whether this unit meets your hold-up requirement. At half load the runtime extends to 8.3 minutes and the sealed lead-acid batteries recharge to 90 percent in four hours. Two RB1290X8 replacement cartridges are user-replaceable. Surge protection is rated at 2430 joules and management is via a serial interface with PowerPanel Business software.

Highlights

  • Double-conversion topology delivers clean sine-wave output
  • Unity power factor provides 10000 W from 10000 VA rating
  • User-configurable 200/208/220/230/240 VAC output ±2 %
  • Seven outlets: four L6-20R, two L6-30R, one hardwire terminal
  • Four-hour recharge to 90 % with replaceable RB1290X8 batteries

Specifications

BrandCyberPower
SeriesSmart App Online UPS
ModelOL10KRTHD
International Version120V
Input Voltage Range120-139 VAC for 0-25% Load
140-159 VAC for 0-50% Load
160-179 VAC for 0-75% Load
180-280 VAC for 0-100% Load
Input Frequency40 - 70 Hz
VA Rating10000 VA
Watts10000 Watts
Outlets7
Outlet Type4 x NEMA L6-20R
2 x NEMA L6-30R
1 x Hardwire Terminal Block
Battery TypeSealed Lead Acid
Battery Run TimeRuntime at Full Load: 2.4 min
Runtime at Half Load: 8.3 min
Battery Recharge Time4 Hours (0% to 90% charged)
Battery Replaceable(2) RB1290X8
AlarmsBattery Mode
Low Battery
Overload
UPS Fault
Interface PortSerial
RackmountableYes
Surge Energy Rating2430 Joules
ProtectionUPS Output Cut off Immediately
Input Fuse / Circuit Breaker Protection
Dimensions17.05" x 6.8" x 28.35"
Weight157 lbs.
Shipping weight90.72 kg
Package size889 × 599 × 452 mm

Questions about this item

What comes in the box with the CyberPower OL10KRTHD and what must I buy separately?

The UPS ships with 4 NEMA L6-20R, 2 NEMA L6-30R and a hardwire terminal block. Input cord and network management card are not included.

Which battery module do I need for replacement in this unit?

The unit requires two RB1290X8 sealed lead-acid battery modules for replacement.

What does the 10000 VA / 10000 W rating mean for my connected equipment?

The power factor is 1, so the full 10000 watts is available for real load; double-conversion topology delivers a pure sine wave at 200, 208, 220, 230 or 240 VAC user-configurable.

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.

Also in this aisle

People compared these

Same shelf, same checkout — eight coins and a 30-minute rate lock.