Winland Electronics
Winland Electronics WB-200 Water Detection System 8-28 VAC/DC
Water detection system monitors for leaks or loss of water across up to six sensors with 1 Form C relay output and 8-28 VAC/DC power
- Monitors water presence or absence in critical areas
- Operates on 8 to 28 V DC or 12 to 28 V AC power
- Includes one unsupervised surface sensor with six-sensor capacity
- Sensors reach 200 ft (60.96 m) for two units or 100 ft (30.48 m) for six
- Form C relay output rated 30 V DC or 24 V AC at 1 Amp
Water Detection for Critical Areas
The WaterBug 200 monitors for the presence or absence of water in computer rooms, document storage, warehouses, sump pumps and basements. Sensors activate the alarm when a conductive bridge forms between two contacts. The device includes one standard unsupervised surface sensor and accepts up to six total sensors for expanded coverage.
Sensor Wiring Limits
One to two sensors can be located up to 200 feet (60.96 m) from the device, while three to six sensors can reach up to 100 feet (30.48 m). Use 18 to 22 AWG twisted pair wire for sensor extensions. Power supplied to the unit must not have a connection to earth ground, as this could cause a failure to detect water or a ground fault.
Power and Output Specifications
The unit operates on 8 to 28 V DC at 35 mA or 12 to 28 V AC at 100 mA. Its operating temperature range is 32 to 130 °F (0 to 54 °C) in a non-condensing indoor environment. Output is a single Form C relay contact rated for 30 V DC at 1 Amp resistive or 24 V AC at 1 Amp resistive.
Highlights
- Monitors water presence or absence in critical areas
- Operates on 8 to 28 V DC or 12 to 28 V AC power
- Includes one unsupervised surface sensor with six-sensor capacity
- Sensors reach 200 ft (60.96 m) for two units or 100 ft (30.48 m) for six
- Form C relay output rated 30 V DC or 24 V AC at 1 Amp
Specifications
| Brand | WINLAND ELECTRONICS |
|---|
Questions about this item
Should I buy one sensor or add more for a larger area?
The unit ships with one sensor and supports up to six total. One or two sensors can reach 200 ft (60.96 m); three to six sensors are limited to 100 ft (30.48 m) from the device.
What does the 8 to 28 V power range mean for my installation?
It accepts 8–28 V DC at 35 mA or 12–28 V AC at 100 mA. The supply must not be referenced to earth ground, or detection may fail.
What can the Form C relay actually switch?
The output is rated for 30 V DC at 1 A resistive or 24 V AC at 1 A resistive, suitable for alarm panels or building-automation inputs.