Tripp Lite
Tripp Lite PDUMV30 Metered PDU 30A 120V 24 Outlets 5-15/20R L5-30P 10ft 0U Vertical
Metered 30 A 120 V vertical PDU with digital current readouts per load bank, 24 NEMA 5-15/20R outlets, dual 20 A breakers, and 10 ft L5-30P cord
- TypeMetered
- Rack Size0U
- StyleVertical
- Input Voltage120V
- Maximum Input Current30A
- Input Connector(s)NEMA L5-30P
- Metered display tracks 30A load per bank
- 24 NEMA 5-15/20R outlets across two breakered banks
- 0U vertical design fits 63.75in rack space
- Attached 10ft cord with NEMA L5-30P plug
- 9kW capacity at 120V single-phase power
Metered 30A PDU for 120V racks
This metered power distribution unit delivers 120V single-phase power at up to 30A through a NEMA L5-30P input plug. It is built for data-centre racks that need local current visibility on each load bank.
0U vertical chassis with dual 20A breakers
The 63.75in vertical housing mounts in 0U space and carries 24 NEMA 5-15/20R outlets split across two separately breakered banks. A 10ft attached cord reaches floor PDUs or wall receptacles without extra cabling.
24A continuous limit on a 30A service
Agency derating caps continuous draw at 24A even though the inlet is rated 30A. The pair of digital meters reports amps per bank so you can balance loads before a breaker trips.
Highlights
- Metered display tracks 30A load per bank
- 24 NEMA 5-15/20R outlets across two breakered banks
- 0U vertical design fits 63.75in rack space
- Attached 10ft cord with NEMA L5-30P plug
- 9kW capacity at 120V single-phase power
Specifications
| Brand | Tripp Lite |
|---|---|
| Model | PDUMV30 |
| Type | Metered |
| Rack Size | 0U |
| Style | Vertical |
| Input Voltage | 120V |
| Maximum Input Current | 30A |
| Input Connector(s) | NEMA L5-30P |
| Cord Length | 10 ft |
| Output Voltage | 120V |
| Output Frequency | 50/60Hz |
| Output Connector(s) | 24 5-15/20R |
| Overload Protection | Outlets are arranged in two separately breakered load banks. The top 20A breaker covers outlets on the upper half, the bottom 20A breaker covers outlets on the lower half of the PDU. Each breakered bank covers 12 5-15/20R outlets. |
| Features | 120V 30A Metered Power Distribution Unit (PDU) in 63.75 in. 0U vertical form factor. 30A maximum capacity (Agency derated to 24A) Attached L5-30P input plug with 10-ft. line cord 24 5-15/20R output receptacles accept both 5-15P and 5-20P equipment plugs Outlets are arranged in two separately breakered and metered 20A load banks (each with 12 5-15/20R outlets) Current meters offer the ability to monitor network power consumption levels to prevent mains, generator, UPS or PDU overloads and to ensure proper load balance in complex redundant power applications Pair of easy-to-read, two-c |
| Dimensions | 63.75" x 2.25" x 3.75" |
| Weight | 8.00 lbs. |
| Shipping weight | 4.63 kg |
| Package size | 1645 × 165 × 76 mm |
Questions about this item
What does the 30 A NEMA L5-30P input cap at in real use?
The agency-derated limit is 24 A, so continuous draw should stay at or below that level on the 120 V single-phase feed.
What rack clearance does the 63.75 in vertical chassis need?
It mounts in a 0U vertical slot and requires 63.75 in of clear height, 2.25 in of width and 3.75 in of depth inside the cabinet.
How do the two 20 A breakers map to the 24 outlets during wiring?
The upper breaker protects the top 12 receptacles and the lower breaker protects the bottom 12; balance loads across both banks when plugging in equipment.
New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.