IEC control relay with five normally-open contacts, 10 A AC rating at up to 600 V and 24 V DC coil voltage
- TypeIndustrial Electrical Controls & Automation
- ColorTransparent
- Controls five circuits with a single 24 V DC coil
- Switches up to 10 A on AC loads at 600 V
- Handles 2 A on DC circuits up to 600 V
- Mounts on DIN rail or flat surface for flexible installation
- Runs at 5.4 W with IP2X finger-safe terminals
Schneider Electric CAD50BD IEC Control Relay
The Schneider Electric CAD50BD is an IEC control relay built for industrial electrical control and automation panels. It provides five normally open contacts rated at 10 amperes AC and operates from a 24 volt DC coil consuming 5.4 watts. The relay mounts on DIN rail or a flat surface and uses screw clamp terminals for secure wiring. Its silver nickel contacts ensure reliable switching in demanding environments.
Suitable applications and limitations
This relay suits panels that require a 24 volt DC coil and five normally open power contacts for AC loads up to 10 amperes at 600 volts. It fits installations with DIN rail or surface mounting and an IP2X protection rating. Buyers who need a different coil voltage, normally closed contacts, a higher contact count, or a different terminal style should look at alternative relay models.
Deciding specification: 24 volt DC coil voltage
The single specification that determines compatibility is the 24 volt DC coil voltage. The control circuit supplying the relay must match this exact voltage; a mismatch will prevent operation or damage the coil. Verify your control supply before ordering.
Highlights
- Controls five circuits with a single 24 V DC coil
- Switches up to 10 A on AC loads at 600 V
- Handles 2 A on DC circuits up to 600 V
- Mounts on DIN rail or flat surface for flexible installation
- Runs at 5.4 W with IP2X finger-safe terminals
Specifications
| Brand | SCHNEIDER ELECTRIC |
|---|---|
| Type | Industrial Electrical Controls & Automation |
| Color | Transparent |
Questions about this item
What DIN rail width and panel depth does the 3.66 in deep body need?
It mounts on standard DIN rail or surface; the housing is 1.77 in wide, 3.03 in high and 3.66 in deep, so allow that envelope in the panel.
Which terminals accept the coil and contact wires, and what mistake trips up installers?
Screw-clamp terminals take both 24 V DC coil leads and the five NO contact wires; the common error is reversing coil polarity on the DC coil.
When should the silver-nickel contacts be inspected or the relay swapped?
Plan a check at the 140 °F maximum ambient rating or after heavy 10 A AC / 2 A DC switching cycles; replace if contact resistance rises or the coil draws more than 5.4 W.