Fans
Fans D4E225-CC01-30 230 V 50 Hz 540 W industrial cooling fan
A 230 V AC double-inlet centrifugal blower with a 540 W motor, IP44 rating and 16 µF capacitor for industrial cooling
- Double-inlet design boosts airflow efficiency
- IP44-rated motor ensures sealed, maintenance-free operation
- Runs on 230 V 50 Hz single-phase power
- Draws 2.4 A at 540 W rated load
- Operates from -25 °C to 30 °C ambient
What this industrial blower is
The Fans D4E225-CC01-30 is a double-inlet centrifugal blower built for 230 VAC 50 Hz mains supply. Its external-rotor motor draws 2.4 A at 540 W and spins at 1210 rpm, delivering airflow against a minimum 250 Pa back-pressure. The IP44-rated motor uses Class B insulation and is permanently sealed for maintenance-free operation in ambient temperatures from -25 °C to 30 °C.
Bundled capacitor and terminal strip
A 16 µF 400 VDB capacitor rated to the S2 (CE) standard ships pre-wired with a terminal strip, so the blower can be connected directly without sourcing a separate run-capacitor. The galvanized steel housing is rivet-mounted and both volute sides open for cleaning, while the forward-curved multi-blade impeller and ball bearings allow installation in any orientation.
Who should use it and who should not
This unit suits engineers integrating forced-air cooling into ABB inverter cabinets or similar HVAC systems that require a compact, rugged blower with a built-in capacitor. It is not suitable for installations that cannot guarantee at least 250 Pa of static back-pressure, nor for environments exceeding 30 °C ambient or requiring variable-speed control not mentioned in the data.
Highlights
- Double-inlet design boosts airflow efficiency
- IP44-rated motor ensures sealed, maintenance-free operation
- Runs on 230 V 50 Hz single-phase power
- Draws 2.4 A at 540 W rated load
- Operates from -25 °C to 30 °C ambient
Specifications
No published specifications for this item yet.
Questions about this item
Does the motor bearing or capacitor require periodic replacement on the D4E225-CC01-30?
The blower uses a sealed ball-bearing motor and a 16 µF 400 VDB capacitor; the unit is described as maintenance-free with no user-replaceable parts listed.
What is the minimum static pressure the D4E225-CC01-30 must maintain to avoid motor overload?
The supplier specifies a minimum back pressure of 250 Pa; operating below this level can cause motor overload.
How much heat and noise should I expect when the fan runs continuously at 230 V 50 Hz?
Continuous draw is 540 W at 2.4 A; the motor is IP44 rated for ambient temperatures from -25 °C to 30 °C, and the double-inlet design reduces noise compared to single-inlet units.