We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

Fans

Fans D4D225-GH02-01 double inlet centrifugal blower

SKU CH-4HX4-H2EFA

A double inlet centrifugal blower moving up to 35,000 m³/h with 400 V three-phase power and CE approval

  • High airflow capacity up to 35,000 m³/h
  • Wide operating range from -40 °C to 70 °C
  • Three-phase 400 V AC motor with Y wiring
  • 100 % speed control via analog or serial interface
  • Compact external-rotor design for forced motor cooling

Industrial three-phase centrifugal blower

The Fans D4D225-GH02-01 is a double-inlet centrifugal blower built for HVAC and industrial air-handling systems. It suits engineers and maintenance teams who need a compact, externally mounted motor design that delivers high airflow in tight plant rooms or ductwork.

Three-phase 400 VAC power and speed envelope

This unit runs on a 400 VAC three-phase supply at either 50 Hz or 60 Hz, drawing 2.1 A at 50 Hz and 2.3 A at 60 Hz with a starting current of 4.64 A. Speed reaches 1230 rpm at 50 Hz and 1360 rpm at 60 Hz, while power consumption is rated at 1140 W and 1280 W respectively. Operation is approved from -40 °C up to 70 °C at 50 Hz and 50 °C at 60 Hz, and the blower can develop at least 150 Pa of back pressure at the higher frequency.

Airflow capacity that defines the fit

Maximum airflow reaches 35000 m³/h, which is the single figure that determines whether this blower matches the duct sizing and ventilation load of your project. Buyers who need lower or higher volume should select a different model.

Highlights

  • High airflow capacity up to 35,000 m³/h
  • Wide operating range from -40 °C to 70 °C
  • Three-phase 400 V AC motor with Y wiring
  • 100 % speed control via analog or serial interface
  • Compact external-rotor design for forced motor cooling

Specifications

No published specifications for this item yet.

Questions about this item

Should I choose the 50 Hz or 60 Hz operating mode for this D4D225-GH02-01 blower?

The nameplate lists both 50 Hz and 60 Hz ratings. At 50 Hz the fan runs at 1230 rpm with 1140 W input and 2.1 A draw; at 60 Hz it runs at 1360 rpm with 1280 W input and 2.3 A draw. Select the frequency that matches your local mains supply.

What does the 1140 W power rating mean for daily operation of this centrifugal blower?

At 400 VAC three-phase and 50 Hz the motor draws 1140 W continuously. Starting current reaches 4.64 A, so size your supply and protection for that inrush.

How does the three-phase 400 VAC Y-wiring affect installation of this D4D225-GH02-01 unit?

The blower requires a 400 VAC three-phase supply wired in star (Y) configuration. It runs at 50 Hz or 60 Hz, draws 2.1 A or 2.3 A respectively, and meets CE approval.