BFKK
BFKK 1762-IQ16 MicroLogix 16 PT 24VDC Input Module power adapter
16-point 24 V DC sink/source input module for MicroLogix PLCs with 10–30 V operating range and 1200 V AC isolation
- 16-point 24 V DC input module for MicroLogix PLCs
- Wide 10-30 V DC operating range suits varied supplies
- 4 W max heat dissipation keeps panels cool
- Two isolated groups of eight inputs protect backplane
- IEC Type 1 compatibility with 1200 V AC isolation test
MicroLogix 1762-IQ16 input module
The Allen-Bradley 1762-IQ16 is a MicroLogix PLC input module providing sixteen 24 V DC sink/source points. It operates on a 10 to 30 V DC supply with a maximum heat dissipation of 5.4 W at 30 V DC. The module draws 70 mA at 5 V DC from the backplane and offers IEC Type 1 input compatibility.
Suits 24 V DC discrete sensing.
This module suits systems monitoring 24 V DC discrete devices such as limit switches or proximity sensors. The two isolated groups of eight inputs each share a common reference. Buyers needing analog signal acquisition, AC voltage detection, or more than sixteen points per module should consider other I/O types.
16 inputs at 10-30 V DC
The decisive specification is the sixteen 24 V DC inputs rated for 10 to 30 V DC operating range with 75 V DC working voltage isolation between field and backplane. Input group to backplane isolation is verified at 1200 V AC and 1697 V DC. This defines compatibility with 24 V DC field devices and panel voltage withstand requirements.
Highlights
- 16-point 24 V DC input module for MicroLogix PLCs
- Wide 10-30 V DC operating range suits varied supplies
- 4 W max heat dissipation keeps panels cool
- Two isolated groups of eight inputs protect backplane
- IEC Type 1 compatibility with 1200 V AC isolation test
Specifications
No published specifications for this item yet.
Questions about this item
How many input points does the 1762-IQ16 provide and what voltage range do they accept?
The module provides 16 input points accepting 10 to 30 Volts DC sink/source signals with a minimum on-state voltage of 10 Volts DC and maximum off-state voltage of 5 Volts DC.
What is the maximum heat dissipation of the 1762-IQ16 when powered at 30 Volts DC?
At 30 Volts DC the module dissipates a maximum of 5.4 Watts; at 26.4 Volts DC the maximum is 4.3 Watts.
What isolation rating does the 1762-IQ16 provide between input groups and the backplane?
Input groups to backplane isolation is verified at 1200 Volts AC for 1 second and 1697 Volts DC for 1 second with a 75 Volts DC working voltage and IEC Class 2 reinforced insulation.