We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

Appleton Century Crofts

Appleton Century Crofts EYDM-200 IMC Sealing Conduit 2 in Threaded Iron Silver

SKU CH-EPB6-JD3N0

Vertical sealing conduit fitting with 2-inch threaded iron ends rated for hazardous locations Class I, II and III

  • TypeCable Management & Conduit
  • Seals conduit against gas and flame passage with Class I Division 1 rating
  • Vertical 2 in threaded iron fitting connects IMC and RMC conduit systems
  • Male-to-female NPT threads enable secure hazardous-location conduit transitions
  • 6 1/8 in overall length fits standard 2 in trade size installations
  • Silver iron construction provides durability for Class II and III hazardous areas

EYDM-200 Sealing Conduit for Hazardous Locations

This Appleton sealing conduit fitting is built for vertical runs in hazardous areas rated Class I Division 1 and 2, Groups B, C, D, Class II Division 1 and 2, Groups E, F, G, and Class III. It stops gases, vapours or flames from travelling between conduit sections. The 2 in trade size suits IMC and RMC systems. It is intended for electricians and plant engineers working in classified industrial environments.

Threaded Iron Construction with Male-to-Female Ends

The iron body carries a silver finish and measures 6 1/8 in overall length. One end offers a 2 in FNPT female thread while the other provides a 2 in MNPT male thread, allowing direct inline connection without extra couplings. Vertical orientation is specified, so the fitting must be mounted upright to maintain its sealing performance. Installers should verify conduit alignment before tightening.

Sealing Compound Required for Compliance

The fitting arrives as a single component without sealing compound or packing fibre included. Users must supply an approved sealing material to complete the hazardous-location barrier. No additional software, gaskets or mounting hardware are bundled. Buyers needing horizontal or angled sealing fittings should select a different model.

Highlights

  • Seals conduit against gas and flame passage with Class I Division 1 rating
  • Vertical 2 in threaded iron fitting connects IMC and RMC conduit systems
  • Male-to-female NPT threads enable secure hazardous-location conduit transitions
  • 6 1/8 in overall length fits standard 2 in trade size installations
  • Silver iron construction provides durability for Class II and III hazardous areas

Specifications

TypeCable Management & Conduit
BrandAPPLETON ELECTRIC

Questions about this item

What thread standard does the 2 in EYDM-200 use and what does it seal against?

It uses 2 in FNPT x 2 in MNPT threads and prevents passage of gases, vapours or flames between conduit sections in hazardous locations.

What physical space and orientation are required to mount this fitting?

The vertical fitting has an overall length of 6 1/8 in and is designed for vertical conduit runs using compatible 2 in IMC or RMC conduit.

How is the sealing compound installed and what common step is missed?

After threading the male end into the conduit hub, the chamber is filled with approved sealing compound; the step often missed is allowing the compound to fully cure before energising the circuit.