NPP Power Co., Ltd
NPP Power Co., Ltd HR1222W 12V 5Ah High Rate Sealed Lead Acid UPS Battery
A 12 V 5 Ah high-rate sealed lead-acid battery with F2 terminals, rated for 1200 cycles and a five-year float life at 68 °F
- SpecificationsNominal Voltage: 12 volt / HR1221W Rated Capacity (20 hour r
- TypeRechargeable Batteries
- Battery Pack1-pack
- FeatureHigh Rate Sealed Lead Acid UPS Battery
- Designed floating life of 5 years at 68°F
- Up to 1200 charge cycles for long service
- 126 watts per cell high-rate discharge capability
- UL, CE, IEC and ISO certifications ensure safety
- Non-spillable AGM design allows flexible mounting
HR1222W 12V 5Ah UPS Battery
The NPP HR1222W is a 12 volt, 5 Ah high-rate sealed lead-acid battery built for UPS and standby power. It uses AGM technology, requires no maintenance and is non-spillable for flexible mounting. The unit carries UL, CE, IEC, ISO14001, ISO19001, OHSAS18000 and TLC certifications and is rated for up to 1200 cycles at 68 Fahrenheit.
Fit for UPS and standby use only
This battery suits installations that need a 12 V high-rate AGM block with F2 terminals and a 5 Ah rating. It does not suit buyers who need a larger capacity, a different terminal type, a lithium chemistry or a deep-cycle design.
5 Ah at 20-hour rate decides fit
The rated capacity is 5 Ah at the 20-hour rate, with a maximum charge current of 1.5 A and a 5-second discharge capability of 75 A. Float voltage is 13.5 to 13.8 V and cyclic charge voltage is 14.5 to 15 V. Verify that your UPS or charger matches these parameters before purchase.
Highlights
- Designed floating life of 5 years at 68°F
- Up to 1200 charge cycles for long service
- 126 watts per cell high-rate discharge capability
- UL, CE, IEC and ISO certifications ensure safety
- Non-spillable AGM design allows flexible mounting
Specifications
| Brand | NPP |
|---|---|
| Model | HR1222W |
| Part Number | NP-HR1222W |
| Specifications | Nominal Voltage: 12 volt / HR1221W Rated Capacity (20 hour rate): 5/5.5 amp |
| Type | Rechargeable Batteries |
| Battery Pack | 1-pack |
| Feature | High Rate Sealed Lead Acid UPS Battery |
Questions about this item
Does my UPS need F2 terminals to accept this HR1222W battery?
The unit ships with T1/T2 terminals, so it fits UPS units that use the standard F2 spade connector.
Will the 75 A maximum discharge current work with my existing UPS that draws less than 75 A?
Yes, the 75 A peak rating covers short surges, and any UPS drawing below that limit will operate normally.
How can I confirm the battery is holding charge after installation?
Measure the float voltage; a healthy cell reads between 13.5 V and 13.8 V when the UPS is on mains power.